SCONI-AR-PWR電源避雷器POWER ARRESTER
Order information
SCONI – AR – PWR
General specification
Mounting drawing
Item Specification
Max Line
Voltage (P-100)/120V AC, (P-200)/250V AC
Discharge
Voltage
L to L – (P-100)/190V, (P-200)/410V
L to G – (P-100)/410V, (P-200)/800V
Max Surge
Voltage (P-100)/400V, (P-200)/800V
Internal
Series Res Approx 0.4Ω
Discharge
Current 1000A(8 x 20 ㎲)
Max Load
Current 1.0A
Response
Time Less than 0.1 ㎲
L to L : Less than Leakage an 1mA(150V DC)
Current L to G : Less than 1mA(300V DC)
Operating
Temperature -5 ~ 55℃
Operating
Humidity 10 ~ 90% RH (non-condensing)
Rail Type : W 23 x H 79 x D 83 mm
Dimension
Panel Type : W 23 x H 80 x D 80 mm
General
This model supplies 1A AC power and eliminates
most harmonics which is composed of lightning
surge.
Exceed the peak voltage of surge is discharged
By element and it contains 2A fuse for protect
Power supply in case of occurrence of break down.
20 62