*臺儀FU96-20300B溫控儀湖南代理商
產品資料:
saved in the PLC to the LCD Option Board.
Language Changing the display language (Japanese/English)
Other functions*臺儀FU96-20300B溫控儀湖南代理商
? Setting the time of the PLC's built-in clock
? Reading system data (e.g., unit version and lot number)
? Setting the backlight lighting time
? Adjusting LCD contrast
? Reading cycle time (e.g., average, maximum, and minimum)
? Clearing data for the LCD Option Board
CP1W-40EDR/40EDT/40EDT1/32ER/32ET/32ET1/20EDR1/20EDT/20EDT1/16ER/16ET/16ET1/8ED/8ER/8ET/8ET1 Expansion I/O Units
Expansion I/O Units can be connected to the CPU Unit to configure the required number of I/O points.
●DC Inputs (CP1W-40EDR/40EDT/40EDT1/20EDR1/20EDT/20EDT1/8ED)
Item Specifications
Input voltage 24 VDC +10%/?15%
Note: 1. Do not apply a voltage exceeding the rated voltage to an input terminal.
2. Can be set in the PLC Setup to 0, 0.5, 1, 2, 4, 8, 16 or 32 ms. The CP1W-
40EDR/EDT/EDT1 are fixed at 16 ms.
Input impedance 4.7 kΩ
Input current 5 mA typical
ON voltage 14.4 VDC min.
OFF voltage 5.0 VDC max.
ON delay 0 to 32 ms max. (Default: 8 ms) (See note 1.)
OFF delay 0 to 32 ms max. (Default: 8 ms) (See note 1.)
Note: Under the worst conditions, the service life of output contacts is as shown on
the left. The service life of relays is as shown in the following diagram as a
guideline.
0 55
Ambient temperature (?C)
43
Output load current (%)
50
100
300
500
200
100
50
30
20
5
3
2