T2550常用模件類型 - AI2二通道模擬量輸入卡,可冗余或單重配置 - AI3三通道模擬量輸入卡,可冗余或單重配置 - AI4四通道模擬量輸入卡,可冗余或單重配置 AI2 analogue input - 2 channel This analogue input module is used to monitor analogue signals from a wide range of plant sensors, The mA and TC inputs each require the appropriate Thermal Unit. The second channel of the A12 has a special high impedance range for use with the zirconia probe inputs. No of channels: 2 Input types: TC, RTD, Volts, mA, mV, Potentiometer, Pyrometer, Zirconia probe mV range: -150mV to +150mV at input impedance >100MΩ mA range: -22mA to +22mA with 5Ω burden in the terminal unit Volts range: -10.2V to +10.2V at input impedance 303kΩ RTD support: Support for 2, 3 and 4 wire resistance thermometer devices Ohms range: 0 to 600Ω 3- or 4-wire lead compensation Hi Ohms range: 0 to 5kΩ 3- or 4-wire lead compensation Pot range: 5% to 95% ‘rotation’ of 100Ω to 5kΩ pot AI3 analogue input - 3 channel Provides three isolated current input channels specifically designed to meet the requirements of modern two wire transmitters. Each channel has its own isolated 24V supply for 3-wire transmitter excitation. Each channel is protected against short circuit (with 24V dc supply on) and utilises a sophisticated trip and try system where the module senses over current and cuts the power, after a period the circuit checks for continued circuit malfunction. The module can be optionally fitted with disconnects to allow isolation of an individual input to allow work on the loop to continue safely. No of channels: 3 Input range: -28mA to +28mA AI4 analogue input - 4 channel This analogue input module is used to monitor analogue signals from a wide range of plant sensors. The mA and TC inputs each require the appropriate Terminal Unit. No of channels: 4 Input types: TC, mV, mA, Pyrometer mV range: -150 - +150mV at input impedance >100MΩ mA range: -22 - +22mA with 5Ω burden in the terminal unit |